Shinwoo

SHINWOO
AIR CONDITIONING CO., LTD.
KR admin
  • Product Info
  • Fan Coil Unit
  • Ceiling Concealed Type
  • Product Info

    홈페이지를 방문해주셔서 감사합니다.

    Fan Coil Unit
    Ceiling Concealed Type

    We aim to promote Korea's air conditioning technology worldwide
    and grow into a globally competitive company through sustainable innovation.

    Ceiling Concealed Type Low-Noise, Ceiling Concealed Type High-Pressure, Ceiling Concealed Type High-Capacity, High-Pressure, Ceiling Concealed Type
    • Ceiling Concealed Type

    Product Features

    An electric motor with low vibration, low noise, and a long-lifespan die-cast housing has been applied.

    • As it is concealed inside the ceiling, indoor space can be utilized effectively.

      Able to apply 4-pipe configuration.Option

      With the application of a BLDC motor as a standard specification power consumption can be reduced by more than 30% compared to an AC motor, with low power and high efficiency.Option

    • For energy savings, installation of On/Off valves for each product is recommended.Option

      These control the flow in coordination with the unit's operation preventing condensation issues during cooling, and reducing unnecessary preventing condensation of the circulation pump.

      Both central control and group control are available.Option

      Central control can be achieved through power line communication and S-485 communication

      Group control of up to 16 units can be performed using a wired remote controller.

      The use of UV lamps offers outstanding effects in terms of sterilization, antibacterial properties, and odor removal, and addressing sick building syndrome.Option

      Korean Patent Registration No. 10-1147406

    Ceiling Concealed Type

    • MODEL A B (Outlet) C (Hanger Position) D (Motor) E (Fan)
      SFC-20CM 540 480 510 1 1
      SFC-30CM 660 600 630 1 1
      SFC-40CM 780 720 750 1 2
      SFC-60CM 1020 960 990 1 2
      SFC-80CM 1260 1200 1230 2 3
      SFC-120CM 1500 1440 1470 2 4
    • No. DESCRIPTION MAT'L Q'TY REMARK
      1 WATER OUTLET BS 1 PF 3/4"(20A)
      2 AIR VENT BS 1 PT 1/8"(Manual)
      3 WATER INLET BS 1 PF 3/4"(20A)
      4 DRAIN PAN GI 1 -
      5 FAN IMPELLER ABS E SIROCCO FAN
      6 FAN & HOUSING ABS E -
      7 AIR FILTER Vinyl Chloride 1 Submerged Type
      8 MOTOR ASSY D 1Ø 220V 60Hz
      9 DRAIN CONNECTION - 1 NIPPLE 1/2"(15A)
      10 HEAT & COOLING COIL CU-AL 1 SLIT FIN

    Standard Specifications

    Horizontal Scroll
    Category Specifications SFC-20CM SFC-30CM SFC-40CM SFC-60CM SFC-80CM SFC-120CM
    Capacity Capacity Conditions A B A B A B A B A B A B
    Cooling Capacity W 2,790 2,120 3,700 2,810 5,360 4,050 7,220 5,490 10,440 7,870 13,610 10,260
    Kcal/h 2,400 1,820 3,180 2,420 4,610 3,480 6,210 4,720 8,980 6,770 11,700 8,820
    Heating Capacity W 5,640 3,470 7,780 4,770 10,990 6,710 14,330 8,760 21,240 12,950 23,640 14,340
    Kcal/h 4,850 2,980 6,690 4,100 9,450 5,770 12,320 7,530 18,270 11,140 20,330 12,330
    Flow Rate ℓ/min 8.1 6.0 10.7 8.0 15.4 11.5 20.8 15.7 30.0 22.4 39.1 29.3
    Head Loss mAq 0.7 0.4 1.6 0.9 4.4 2.4 3.5 2.0 9.5 5.3 16.8 9.4
    Fan Blower Type Double Suction Multi-Blade Type(SIROCCO FAN)
    SIZE mm Ø145 X L165 Ø145 X L200 Ø145 X L165 Ø145 X L200 Ø145 X L200 Ø145 X L200
    Airflow Volume ㎥/min 5.7 8.5 11.3 17 22.6 34
    Drive Type Direct Drive Motor
    Quantity EA 1 1 2 2 3 4
    Motor Type AC Semi-Enclosed Type (6 poles, Class B insulation)
    Power Consumption W 45 55 70 85 55 + 85 85 X 2
    Quantity EA 1 1 1 1 2 2
    Heat Exchanger Type Integrated Multi-Pass Cross Finned Tube(Slit Fin)
    Pipe Inlet A PF 3/4" (20A)
    Outlet A PF 3/4" (20A)
    Drain NIPPLE 1/2"(15A)
    External Material Galvanized Steel Sheet
    Air Volume Control Strong, Medium, Weak 3-Stage Rotary Switch
    Power Supply Single Phase 220V 60HZ
    AIR FILTER Vinyl Chloride (Submerged)
    Product Weight Kg 15 17 20 24 32 40
    * Note 1. Capacity Condition A - Cooling Capacity When indoor air is DB 27°C, WB 21°C, and inlet water temperature is 5°C Heating Capacity When indoor air is 18°C, and inlet water temperature is 80°C
    2. Capacity Condition B - Cooling Capacity: When indoor air is DB 27°C, WB 19.5°C, and inlet water temperature is 7°C Heating Capacity: When indoor air is 21 °C, and inlet water temperature is 60°C