Fan Coil Unit
Facility Cultivation
We aim to promote Korea's air conditioning technology worldwide
and grow into a globally competitive company through sustainable innovation.

Excellent heat transfer performance and easy installation
It can be installed not only in Facility Cultivation houses but also in barns pigsties, poultry houses, and greenhouses.
Customized design is possible to meet the demands of consumers.

| MODEL | A | B | C |
|---|---|---|---|
| SFC-30CU | 590 | 344 | 1 |
| SFC-60CU | 940 | 564 | 2 |
| No. | DESCRIPTION | MAT'L | Q'TY | REMARK |
|---|---|---|---|---|
| 1 | CASING | GI | 1 | - |
| 2 | WATER OUTLET | BS | 1 | PF 3/4"(20A) |
| 3 | AIR VENT | BS | 1 | PT 1/8'(Manual) |
| 4 | WATER INLET | BS | 1 | PF 3/4"(20A) |
| 5 | DRAIN PAN | GI | 1 | - |
| 6 | DRAIN CONNECTION | - | 1 | NIPPLE 1/2"(15A) |
| 7 | Propeller | AL | 1 | AXIAL FAN |
| 8 | MOTOR | ASS’Y | C | 1Ø 220V 60Hz |
| 9 | Fixed Mesh | ASS’Y | C | - |
| 10 | COIL ASSY | AL | 1 | - |
| Category | Specifications | SFC-30CUD | SFC-60CUD | |||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| Capacity | Capacity Conditions | A | B | A | B | |||||||||
| Cooling Capacity | W | 12,250 | 9,300 | 27,560 | 20,930 | |||||||||
| Kcal/h | 10,540 | 8,000 | 23,700 | 18,000 | ||||||||||
| Heating Capacity | W | 20,950 | 12,790 | 47,500 | 29,070 | |||||||||
| Kcal/h | 18,020 | 11,000 | 40,840 | 25,000 | ||||||||||
| Flow Rate | ℓ/min | 35.2 | 26.7 | 78.6 | 60.1 | |||||||||
| Head Loss | mAq | 4.6 | 2.7 | 7.6 | 4.5 | |||||||||
| Fan Blower | Type | Propeller | ||||||||||||
| SIZE | mm | Ø300 | ||||||||||||
| Airflow Volume | ㎥/min | 66 | 130 | |||||||||||
| Drive Type | Direct Drive Motor | |||||||||||||
| Quantity | EA | 1 | 2 | |||||||||||
| Motor | Type | AC Semi-Enclosed (4 poles, Class E insulation) | ||||||||||||
| Power Consumption | W | 20 | 45 | |||||||||||
| Quantity | EA | 1 | 2 | |||||||||||
| Heat Exchanger | Type | Integrated Multi-Pass Cross Finned Tube(Slit Fin) | ||||||||||||
| Pipe | Inlet | A | PF 3/4" (20A) | |||||||||||
| Outlet | A | PF 3/4" (20A) | ||||||||||||
| Drain | NIPPLE 1/2" (15A) | |||||||||||||
| External Material | Galvanized Steel Sheet | |||||||||||||
| Power Supply | Single Phase 220V 60HZ | |||||||||||||
| Product Weight | Kg | 8 | 16 | |||||||||||
| * Note | 1. Capacity Condition A - Cooling Capacity When indoor air is DB 27°C, WB 21°C, and inlet water temperature is 5°C Heating Capacity When indoor air is 18°C, and inlet water temperature is 80°C 2. Capacity Condition B - Cooling Capacity: When indoor air is DB 27°C, WB 19.5°C, and inlet water temperature is 7°C Heating Capacity: When indoor air is 21°C, and inlet water temperature is 60°C |
|||||||||||||