홈페이지를 방문해주셔서 감사합니다.
Ventilation Unit
Ventilation Unit | High-Efficiency ABS
We aim to promote Korea's air conditioning technology worldwide
and grow into a globally competitive company through sustainable innovation.


| No. | DESCRIPTION | MAT'L | Q'TY | REMARK |
|---|---|---|---|---|
| 1 | CASING | ABS | 1 | - |
| 2 | ACCESS DOOR | ABS | 1 | - |
| 3 | FAN & MOTOR | - | 2 | BLDC MOTOR |
| 4 | HEAT EXCHANGER | PULP | 1 | Special Processed Pulp for Heat Exchange |
| 5 | PRE-FILTER | - | 2 | Nonwoven Fabric |
| 6 | MEDIUM FILTER | - | 1 | Synthetic Fiber |
| 7 | DUCT FLANGE | ABS | 2 | F (SA, RA) |
| 8 | MD | ABS | 1 | F (EA) |
| 9 | BDD | ABS | 1 | F (OA) |
| 10 | CONTROL BOX | ABS | 1 | PCB Included |
| MODEL | W | L | H | A | B | D | F |
|---|---|---|---|---|---|---|---|
| SW-100SCNBP | 529 | 493 | 220 | 449 | 485 | 220 | Ø125 |
| SW-150SCNBP | 602 | 630 | 250 | 582 | 552 | 254 | Ø150 |
| Category | Unit | SW-100SCNBP | SW-150SCNBP | |||||||
|---|---|---|---|---|---|---|---|---|---|---|
| Airflow Volume | CMH | Strong | Medium | Weak | Strong | Medium | Weak | |||
| 150 | 150 | 120 | 200 | 200 | 160 | |||||
| Power Consumption | W | 65 | 52 | 48 | 90 | 80 | 65 | |||
| Static Pressure | mmAq | 10 | 7 | 10 | 7 | |||||
| Product Size(W×L×H) | mm | 529×493×220 | 602×630×250 | |||||||
| Duct Diameter | mm(Ø) | 125 | 150 | |||||||
| Noise* | dB | 45dB(A) or less | ||||||||
| Power Supply | - | Ø1 / 220V / 60Hz | ||||||||
| Heat Recovery Rate | % | Heating : 70 / Cooling : 45 | Heating : 70 / Cooling : 45 | |||||||
| Heat Exchanger | - | Square Plate Heat Exchanger | ||||||||
| Air Volume Control Method | - | ON/OFF, 3-Stage Control | ||||||||
| Filter | - | PRE FILTER, MEDIUM FILTER | ||||||||
| Casing | - | ABS | ||||||||
| Optional Specification | - | Antibacterial, Deodorization, Wired Remote Control, etc. | ||||||||
| * The noise level indication is based on the installation and completion of finishing work on-site. | ||||||||||